Bộ giám sát năng lượng sách tay 3 pha 500A ICP DAS PPMS-133D-RCT500P CR

Chia sẻ:
Mã sản phẩm: PPMS-133D-RCT500P
Thương hiệu: ICP DAS
Tình trạng:

Portable Power Monitoring Suitcase

Liên hệ
Mô tả

Bộ giám sát năng lượng sách tay 3 pha 500A ICP DAS PPMS-133D-RCT500P CR

Feature

• True RMS Power Measurements
• Energy Analysis for 3P4W, 3P3W, 1P3W, 1P2W
• Voltage Measurements Up to 500 V
• Current Measurements up to 500 A
• Harmonic data capture (up to 31th order)
• Provide 7" Touch Panel for On-Site operations
• Support SNMP Protocol
• Temperature and Humidity Data Logger

Introduction

Portable Power Management Suitcase can measure single to three-phase lines with a high degree of precision and accuracy. The PPMS-133D-RCT500P Rogowski Coil CT power meters are designed to measure demand and harmonics, which are important for energy management, as well as basic electrical parameters such as voltage, current, power, power factor, and integrated power (watthours). PPMS-133D-RCT500P is equipped with built-in Web Server that allows direct connections via browsers to the PPMS-133D-RCT500P for viewing power data and setting up the system parameters. PPMS-133D-RCT500P allows connect to SCADA software to get realtime power data.

Application

• Generator monitoring
• Switchgear distribution systems
• Energy Management
• Power quality analysis

Specifications

AC Power Measurement
Wiring 3P4W-3CT, 3P3W-2CT, 3P3W-3CT, 1P2W-1CT, 1P3W-2CT
Loops Three-phase
Input Voltage 10 ~ 500 V
Input Current CTØ55 mm (5 A ~ 500 A)
Input Frequency 50/60 Hz
W Accuracy Better than 2% (PF=1)
Power Parameter Measurement True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent
Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency
Data Update Rate 1 Second
CT
Includes CTs 3
Type Rogowski
Max. Current 500 A
Inside Diameter 55 mm
Leading Cable 4 m
Temperature Measurement
Range -20 ~ +60°C (-4 ~ +140°F)
Resolution 0.1°C
Accuracy Typical: ±0.4°C
Precision ±0.1°C
Humidity Measurement
Range 10 ~ 95% RH
Resolution 0.1°C
Accuracy Typical: ±3% RH @ 20 ~ 80% RH
Precision ±0.1°C
Dew Point
Range Calculated using temperature and relative humidity
Resolution 0.1°C
Power
Input Range 85 ~ 264 VAC

Download

Datasheet

Documents

Ordering Information

PPMS-133D-RCT500P     CR  Portable Power Monitoring Suitcase,500A Rogowski Coil CT (RoHS)
(Inside diameter 55 mm; wire lead 4 m)x3