- Tổng tiền thanh toán:
1-ch RTD Input Module with 1 DI and 2 DO
Khi mua hàng tại website của chúng tôi, quý khách sẽ được:
Module RS-485 Modbus RTU 1 kênh đầu vào RTD + 2 kênh DO + 1 kênh DI ICP DAS M-7013P-G CR
Features
Introduction
M-7013P/M-7013PD is a 1-channel RTD Input module that is used for measuring temperatures via an RTD sensor and supports Pt100, Ni120, and Pt1000 types of sensors. The module allows 2/3/4-wire RTD connections and features open-wire detection. In addition, M-7013P(D) also includes 3000 VDC intra-module isolation and supports lead resistance elimination for 3/4-wire connections. The module added support for 1-channel digital input as a 50 Hz event counter and 2-channel digital output as a high/low alarm. M-7013P(D) supports Modbus RTU and DCON protocols, which can be configured via software.
Applications
• Building Automation
• Factory Automation
• Machine Automation
• Remote Maintenance
• Remote Diagnosis
• Testing Equipment
Specifications
CPU Module | |
---|---|
Watchdog Timer | Module, Communication (Programmable) |
Isolation | |
---|---|
Intra-module Isolation | 3000 VDC |
EMS Protection | |
---|---|
EFT (IEC 61000-4-4) | ±4 kV for Power Line |
ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
Surge (IEC 61000-4-5) | ±0.5 kV for Power Line |
LED Indicators | |
---|---|
Status | 1 x Power and Communication |
Analog Input | |
---|---|
Channels | 1 |
Type | RTD |
Sensor Type | Pt100, Pt1000, Ni120 |
Resistance Measurement | 3.2 kΩ Max. |
Resolution | 16-bit |
Accuracy | ±0.05% of FSR |
Sampling Rate | 10 Hz |
Overvoltage Protection | ±120 VDC |
Open Wire Detection | Yes |
3-wire RTD Lead Resistance Elimination | Yes |
Digital Input/Counter | |
---|---|
Type | Dry Contact |
Sink/Source (NPN/PNP) | Source |
ON Voltage Level | Close to GND |
OFF Voltage Level | Open |
Max. Counts | 65535 (16-bit) |
Frequency | 50 Hz |
Overvoltage Protection | ±30 VDC |
Digital Output | |
---|---|
Channels | 2 |
Type | Open Collector, MOSFET |
Sink/Source (NPN/PNP) | Sink |
Load Voltage | +3.5 ~ +50 VDC |
Load Current | 700 mA/Channel |
Overvoltage Protection | 60 VDC |
Overload Protection | 1.4 A |
Short-circuit Protection | Yes |
Power on Value | Programmable |
Safe Value | Programmable |
COM Ports | |
---|---|
Ports | 1 x RS-485 |
Baud Rate | 1200 ~ 115200 bps |
Data Format | (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1) |
Protocol | Modbus RTU, DCON |
Power | |
---|---|
Reverse Polarity Protection | Yes |
Input Range | +10 ~ +30 VDC |
Consumption | 0.6 W |
Mechanical | |
---|---|
Dimensions (mm) | 123 x 72 x 35 (W x L x H) |
Installation | DIN-Rail Mounting |
Environment | |
---|---|
Operating Temperature | -25 ~ +75 °C |
Storage Temperature | -40 ~ +85 °C |
Humidity | 10 ~ 95% RH, Non-condensing |
Download
Ordering Information
M-7013P-G CR | 1-ch RTD Input Module with 1 DI and 2 DO using DCON and Modbus Protocols (Gray Cover) (RoHS) |