Giới thiệu bộ lập trình nhúng Windows PAC-XP-9000-WES7 hãng ICP DAS
The XP-9000-WES7 are WES7 based PACs that combine computing, I/O, and operator interface into a single unit, and provide the perfect solution for integrating HMI, data acquisition and control in an individual PAC. It is equipped with an Intel E3827/E3845 CPU, 1/3/7 I/O expansion slots and a variety of connectives including dual Gigabit Ethernet, VGA , USB port, RS-232 and RS-485 interface. Local I/O slots are available to use our I-9K and I-97K series I/O modules and remote I/O expansions are available to use Ethernet I/O modules and RS-485 I/O modules.
Software Features
WES7 Embedded OS
- Full Win32 API
- Remote Desktop Protocol 5.1
- Silverlight 5
- Enhanced Write Filter
- .NET Framework 3.5 SP1, 4.0, 4.5
- Language support : English, French, German, Italian, Japanese, Korea, Russian, Portuguese, Spanish, Simplified Chinese, Traditional Chinese
Rich Software Solutions
- Visual Studio .Net 2008 and VC solution: SDK as well as demo programs for C#, VB.Net and VC are provided.
- eLogger HMI: A free charge and easy-to-use software to implement HMI and data logger, supporting Modbus TCP/RTU/ASCII master and MQTT protocols. (See more...)
Hardware Features
Powerful CPU Module
- E3845 (1.91 GHz, quad core)/E3827 (1.75 GHz, dual core) CPU
- 2 GB SDRAM (DDR3)
Built-in VGA Port
A built-in VGA port can be directly connected to a regular LCD display. Users can operate the HMI or SCADA software (running on the XP-9000-WES7) with display, keyboard and mouse just as howthey usually did on regular PCs.
64-bit Hardware Serial Number
The 64-bit hardware serial number is unique and individual. Every serial number of XP-9000-WES7 PAC is different. Users can add a checking mechanism to their AP to prevent software from pirating.
Rich I/O Expansion Ability (RS-232/485, USB, Ethernet)
Beside the local I/O slots, XP-9000-WES7 also provides several RS-232/RS-485/USB ports and two Ethernet ports to connect with serial/USB I/O and Ethernet I/O devices.
Dual Watchdog Timer
A system could be hanged up when the OS or the AP fails. There are two watchdogs (OS watchdog and AP watchdog) designed to automatically reset the CPU when the situations happen. The design will increase the reliability of the system.
Dual Ethernet Ports
XP-9000-WES7 provides two Gigabit Ethernet ports. The two Ethernet ports can be used to implement redundant Ethernet communication and separate Ethernet communication (one for global Internet, one for private Ethernet).
Rugged RJ-45 connector for LAN1
The XP-9000-WES7 is equipped with a rugged and dustproof RJ-45 connector on the LAN1 port that is able to provide protection against both liquid and dust contaminants in harsh industrial environments, as well as protection against vibration and shock.
Power/Communication spring clamp terminal connector
The spring clamp terminal block that is used for the Power/Communication connector in the XP-9000-WES7 offers advantages including anti-vibration, stable clamping, and easier installation.
Metal Enclosure
The XP-9000-WES7 features a durable metal casing to provide high levels of impact resistance and flame resistance, and higher protection on EMS or other electromagnetic noises.
Redundant Power Inputs
To prevent the XP-9000-WES7 from failing by the power loss, the power module is designed with two inputs. The XP-9000-WES7 can keep working even one power input fails, and mean while there is a relay output for informing the power failure.
Fanless Design with Wide Operating Temperature Range
With the fanless design for embedded applications, the operating temperature range is -25°C to +75°C for the XP-9x71-WES7 series, as well as -25°C to +60°C for the XP-9x81-WES7 series.
Standard XP-9000-WES7 (Windows Embedded Standard 7 Inside)
The controller supports following software development tools:
1. DLLs of I/O modules for VS.NET 2005/2008
2. OPC server for SCADA software
Model | CPU | System Memory | Non-Volatile Memory | Storage | VGA Resolution |
Ethernet Port |
USB Port | RS-232/ RS-485 |
I/O Slot |
---|---|---|---|---|---|---|---|---|---|
XP-9171-WES7 | E3827 1.75 GHz,dual core | 2 GB DDR3 SDRAM | 128 KB MRAM; 16 KB EEPROM | 32 GB SSD; 16 GB CF card |
1280 x 1024 to 1920 x 1080(16:9); 640 x 480 to 1024 x 768(4:3) |
2 | 4 | 4 | 1 |
XP-9371-WES7 | 3 | ||||||||
XP-9771-WES7 | 7 | ||||||||
XP-9181-WES7 | E3845 1.91 GHz,quad core | 4 GB DDR3 SDRAM | 1 | ||||||
XP-9381-WES7 | 3 | ||||||||
XP-9781-WES7 | 7 |
Local I/O Expansion
I-9K and I-97K series modules are provided for combining a variety of I/O functions within the WP-9000, XP-9000, LX-9000 and LP-9000 programmable automation controllers (PAC). The I-9k series is based on a parallel interface with high communication speed; while the I-97K series is based on a serial interface.
The differences between the two series are listed as follows:
Model | I-9K Series | I-97K Series |
---|---|---|
Communication Interface | Parallel Bus | Serial Bus |
Protocol | - | DCON |
Communication Speed | Fast | Slow |
DI with Latched Function | - | Y |
DI with Counter Input | - | Y (100 Hz) |
Power on Value | Y | Y |
Safe Value | Y | Y |
Programmable Slew-Rate for AO Module | - | Y |
For more information, please go to the following web page. I-9K/I-97K Series I/O Modules
Remote I/O Expansion
Ethernet
The available Ethernet I/O devices are ET-7000, ET-7200, ET-87P4/8-MTCP and I-8KE4/8-MTCP. The PAC can access them in Modbus/TCP protocol. A nModbus.dll is provided for C#, VB.net programming.
RS-485
The PACs are equipped with the RS485 COM ports which enable the transmission rate up to a maximum of 115.2 Kbps. The medium for connection is a twisted-pair, multi-drop, 2-wire RS-485 network that can link I-7000, M-7000, RU-87Pn with high profile I-87K modules. To access M-7000, a nModbus.dll is provided for C#, VB.net programming. To access I-7000 and RU-87Pn with high profile I-87K modules, PACSDK is provided for C#, VB.net, VC and VB programming.
FRnet
FRnet is an innovative industrial field bus that has many special features, such as high-speed deterministic I/O control, real I/O synchronization capabilities, non-protocol communication, and easy programming. With a FRnet communication module (I-8172W), the PAC can link FRnet I/O modules to implement high-speed distributed I/O (FR-2000 series). To access I-8172W, a pac_i8172w.dll is provided for C#, VB.net, VC and VB programming.
CAN Bus
The Controller Area Network (CAN) is a serial communication way, which efficiently supports distributed real-time control with a very high level of security. It provides the error-processing mechanisms and concepts of message priority. These features can improve the network reliability and transmission efficiency. Furthermore, CAN supplies the multi-master capabilities, and is especially suited for networking“intelligent” devices as well as sensors and actuators within a system or a sub-system. With I-8123, I-8124, I-87120, the PAC is able to demonstrate every feature of CAN, CANopen, and DeviceNet.