Cách đấu dây CM1-WG02(A, C, D, E) CM1-WG04A và Loadcell

Chia sẻ:

Cách đấu dây CM1-WG02(A, C, D, E) CM1-WG04A và Loadcell

Q: How to wire CIMON-PLC WG02(A,C,D,E) WG04A and Load cell

A: Refer to the instructions below.

Load Cell Pin Assignment (Also for the 4 Channel)

Number Name Remarks
1 SEN+ Sensor Line+
2 SEN- Sensor Line-
3 SIG+ Measurement Line+
4 SIG- Measurement Line-
5 EXC+ Supply+
6 EXC- Supply

The upper most pin of each channel connector of the load cell module is number 1.
For the 6-wired load cell, connect to the lines corresponding to the wiring diagram as above.

The 4-wired load cell does NOT have SEN+ and SEN– lines.
For the 4-wired load cell, after wiring the 4 lines except SEN+ and SEN–, please SHORT
CIRCUIT the SEN+ <-> EXC+ and SEN– <-> EXC– pins.

[Load cell line color by manufacturers]

Manufacturer 1
EXC+
2
EXC-
3
SIG+
4
SIG-
5
SHIELD
Bongshin, CAS
Fine, DACELL
Red White Green Blue Yellow
(Outer
Cover)
Daesung
KMTL
Red Black White Green Outer Cover
Power MNC Red White Green White Outer Cover
Daisocell Red Blue Green White Black
BLH Green Black White Red Yellow
INTERFACE
KYOWA
P.T
SHINKOH
Red Black Green White Outer Cover
SHOWA
TEAC
Red Blue White Black Yellow
(Outer
Cover)
HUNTLEIGH Green Black Red White Outer Cover

*The wiring line colors can be different for each manufacturer and their load cell models, please refer to the data sheet of the load cell in use.

How to wire WG02(A,C,D,E) WG04A and Load cell