Mô tả

Module 12 kênh đầu vào RTD ICP DAS R-9015 CR

The R-9015 is a 12-channel, 16-bit RTD temperature measurement module with the following features:

  • Supports Multiple RTD Sensors: PT-100, JPT-100 and PT-1000 temperature sensors.
  • High Accuracy: Tolerance ±0.05% FSR to ensure accurate temperature measurement.
  • High/low Alarm: Abnormal channel temperature is alerted immediately to ensure the safety of system operation.
  • Measurement Range & Temperature Offset: Different measurement ranges and temperature offsets can be set according to application requirements to enhance the accuracy and reliability of the measurement results.
  • Channel Disconnection Detection: Ensures safe and stable wiring of the channel.
  • LED Indicator: Displays channel abnormal status and module operation status.

The R-9015 module must be used with a terminal board to connect external signals and supports a terminal board disconnection detection mechanism to ensure wiring stability. It provides 3000 VDC isolation between the power supply and the backplane bus, making it better able to prevent noise interference in industrial environments without affecting the RIO-98x0 system. Additionally, the module supports a redundancy design, allowing the system to continue stable operation even if a single I/O module fails, further enhancing system reliability.

Features

  • 12 RTD input channels
  • User-defined measurement range scaling
  • 16 bit A/D converter
  • Channel disconnection detection
  • Termination board disconnection detection
  • Redundant switching time (< 1 ms)

Applications

  • Building Automation
  • Factory Automation
  • Machine Automation
  • Remote Maintenance
  • Remote Diagnosis
  • Testing Equipment

Specifications

EMS Protection
EFT (IEC 61000-4-4) Yes
ESD (IEC 61000-4-2) Yes
LED Indicators
Status 1 PWR, 1 MOD, 1 ACT, 1 DX, 1 ERR
LED 0~11 for CH High/Low Alarm
LED 16~27 for CH Break Line
Analog Input
Channels 12
Type RTD
Sensor Type Pt100, JPt100, Pt1000
Range Pt100: -200 ~ +850 ℃
JPt100, Pt1000: -200 ~ +630 ℃
Resolution 16 bit
Accuracy ±0.05% FSR (±250 mΩ)
Sampling Rate 1 Samples/sec (Total)
Input Impedance 20 MΩ
Common Mode Rejection 106 dB
Normal Mode Rejection 100 dB
Open Wire Detection Yes
Zero Drift ±0.5 μV/°C
Span Drift ±20 ppm/°C
Isolation 3000 VDC
I/O Expansion
I/O Type RDB-S03 / RDB-D03
Power
Consumption 2 W
Mechanical
Dimensions (mm) 33 x 129 x 130
Environment
Operating Temperature -25 °C ~ +70 °C
Humidity 5 ~ 95% RH, Non-condensing

Download

Datasheet

Documents

Ordering Information

R-9015   CR 12-ch, RTD Input Module (RoHS)