Trang chủ Liên hệ

Kết nối Cimon SCADA và PLC S7 SIEMENS qua Ethernet?

CÔNG TY TNHH THIẾT BỊ ĐO LƯỜNG VÀ ĐIỀU KHIỂN 22/06/2023

Kết nối Cimon SCADA và PLC S7 SIEMENS qua Ethernet?

Q: How to communicate with SCADA via SIEMENS S7 Series PLC Ethernet Connection?
A: When establishing communication blocks from SCADA, you have to make sure that the number of word communication blocks for the DB unit must be the same as that of SIEMENS PLC DB unit in order to properly communicate.

CIMON SCADA và SIEMENS S7 không hỗ trợ truyền thông PROFIBUS và PROFINET.

Thay vào đó, giao thức Ethernet Loader được sử dụng.

Notice that END_STRUCT ends at 100.
For SIEMENS, the communication unit is in Bytes.
For CIMON SCADA, the communication unit is in Word.
Therefore, when you set up the communication block from SCADA,
2 BYTE makes 1 WORD.
In this case, 100 BYTE is 50 WORD.

[CIMON SCADA]

Register the Communication Block as DB address and 50 Word.
If larger number of Word is registered, the communication will not be connected.
If less number of Word is registered, unregistered tags will be displayed as ???? on the CimonX program.
In other words, DBW should be registered as Double Word for SIEMENS.
DBW should be registered as 1 Word for Com. Block in CIMON SCADA.
For example) When setting up 0 – 50 DBW
SIEMENS: 0 – 100
CIMON SCADA: 0 – 50

SIEMENS S7 Series PLC Ethernet Connection with SCADA

Bài viết liên quan